RoTeK-swt-BT-BT-6707-signals-MIB DEFINITIONS ::= BEGIN IMPORTS enterprises, NOTIFICATION-TYPE, OBJECT-TYPE, MODULE-IDENTITY, Integer32 FROM SNMPv2-SMI; rotek MODULE-IDENTITY LAST-UPDATED "202205300000Z" ORGANIZATION "Rotek" CONTACT-INFO " Rotek Customer Support E-mail: support@rotek.ru" DESCRIPTION "BT-6707" REVISION "202205300000Z" DESCRIPTION "" ::= { enterprises 41752 } swt OBJECT IDENTIFIER ::= { rotek 911 } bt-6707 OBJECT IDENTIFIER ::= { swt 7 } signals OBJECT IDENTIFIER ::= { bt-6707 1 } traps OBJECT IDENTIFIER ::= { bt-6707 2 } fwVersion OBJECT-TYPE SYNTAX OCTET STRING MAX-ACCESS read-only STATUS current DESCRIPTION "FWVersion" ::= { signals 1 } restoreSignal OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Restore settings 1 - restore settings" ::= { signals 2 } rebootSignal OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "Reboot device: 1 - reboot" ::= { signals 3 } upsModel OBJECT-TYPE SYNTAX OCTET STRING MAX-ACCESS read-only STATUS current DESCRIPTION "UPS model" ::= { signals 4 } do1 OBJECT-TYPE SYNTAX OCTET STRING MAX-ACCESS read-write STATUS current DESCRIPTION "0 - open relay1 1 - close relay1" ::= { signals 5 } do2 OBJECT-TYPE SYNTAX OCTET STRING MAX-ACCESS read-write STATUS current DESCRIPTION "0 - open relay2 1 - close relay2" ::= { signals 6 } do3 OBJECT-TYPE SYNTAX OCTET STRING MAX-ACCESS read-write STATUS current DESCRIPTION "0 - open relay3 1 - close relay3" ::= { signals 7 } batTest OBJECT-TYPE SYNTAX Integer32 MAX-ACCESS read-write STATUS current DESCRIPTION "0 - cancel test 1-99 - run test to x minutes 100 - run test to 10 seconds 999 - test till charging" ::= { signals 8 } shutdown OBJECT-TYPE SYNTAX OCTET STRING MAX-ACCESS read-write STATUS current DESCRIPTION "Control of shut down UPS load: 0 - stop shut down load n - shut down load in n minutes n: 0.2, 0.3, .., 1, 2, .., 10" ::= { signals 9 } di0 OBJECT-TYPE SYNTAX OCTET STRING MAX-ACCESS read-only STATUS current DESCRIPTION "State of dry input 0 - close dry input 1 - open dry input" ::= { signals 10 } intTemp OBJECT-TYPE SYNTAX OCTET STRING MAX-ACCESS read-only STATUS current DESCRIPTION "Internal temperature" ::= { signals 11 } inFreq OBJECT-TYPE SYNTAX OCTET STRING MAX-ACCESS read-only STATUS current DESCRIPTION "Input frequency, Hz" ::= { signals 12 } inVoltVAC OBJECT-TYPE SYNTAX OCTET STRING MAX-ACCESS read-only STATUS current DESCRIPTION "Input voltage" ::= { signals 13 } outVoltVAC OBJECT-TYPE SYNTAX OCTET STRING MAX-ACCESS read-only STATUS current DESCRIPTION "Output voltage" ::= { signals 14 } power OBJECT-TYPE SYNTAX OCTET STRING MAX-ACCESS read-only STATUS current DESCRIPTION "Power, %" ::= { signals 15 } batCap OBJECT-TYPE SYNTAX OCTET STRING MAX-ACCESS read-only STATUS current DESCRIPTION "Battery capacity, %" ::= { signals 16 } batTime OBJECT-TYPE SYNTAX OCTET STRING MAX-ACCESS read-only STATUS current DESCRIPTION "Rest working time of battery, min" ::= { signals 17 } connectMonitor OBJECT-TYPE SYNTAX OCTET STRING MAX-ACCESS read-only STATUS current DESCRIPTION "Connect status: 0 - normal; 1 - connect fail" ::= { signals 18 } alarms OBJECT-TYPE SYNTAX OCTET STRING MAX-ACCESS read-only STATUS current DESCRIPTION "bit 7 - utility fail bit 6 - battery low bit 5 - bypass/boost or buck active bit 4 - UPS fail bit 3 - UPS Type is Standby (0 is On_line) bit 2 - Test in Progress bit 1 - Shutdown Active bit 0 - Beeper On" ::= { signals 19 } -- DEVICE TRAPS fwVersionUpdate NOTIFICATION-TYPE OBJECTS { fwVersion } STATUS current DESCRIPTION "" ::= { traps 1 } fwVersionUpdated NOTIFICATION-TYPE OBJECTS { fwVersion } STATUS current DESCRIPTION "" ::= { traps 2 } deviceRestored NOTIFICATION-TYPE OBJECTS { restoreSignal } STATUS current DESCRIPTION "" ::= { traps 3 } deviceRebooted NOTIFICATION-TYPE OBJECTS { rebootSignal } STATUS current DESCRIPTION "" ::= { traps 4 } di0Norm NOTIFICATION-TYPE OBJECTS { di0 } STATUS current DESCRIPTION "" ::= { traps 5 } di0Alarm NOTIFICATION-TYPE OBJECTS { di0 } STATUS current DESCRIPTION "" ::= { traps 6 } do1Toggled NOTIFICATION-TYPE OBJECTS { do1 } STATUS current DESCRIPTION "" ::= { traps 7 } do2Toggled NOTIFICATION-TYPE OBJECTS { do2 } STATUS current DESCRIPTION "" ::= { traps 8 } do3Toggled NOTIFICATION-TYPE OBJECTS { do3 } STATUS current DESCRIPTION "" ::= { traps 9 } batteryTemperatureHighNorm NOTIFICATION-TYPE OBJECTS { intTemp } STATUS current DESCRIPTION "" ::= { traps 10 } batteryTemperatureHighAlarm NOTIFICATION-TYPE OBJECTS { intTemp } STATUS current DESCRIPTION "" ::= { traps 11 } lineAlarm NOTIFICATION-TYPE OBJECTS { inVoltVAC } STATUS current DESCRIPTION "" ::= { traps 12 } lineNorm NOTIFICATION-TYPE OBJECTS { inVoltVAC } STATUS current DESCRIPTION "" ::= { traps 13 } lowBatAlarm NOTIFICATION-TYPE OBJECTS { batCap } STATUS current DESCRIPTION "" ::= { traps 14 } lowBatNorm NOTIFICATION-TYPE OBJECTS { batCap } STATUS current DESCRIPTION "" ::= { traps 15 } powerAlarm NOTIFICATION-TYPE OBJECTS { power } STATUS current DESCRIPTION "" ::= { traps 16 } powerNorm NOTIFICATION-TYPE OBJECTS { power } STATUS current DESCRIPTION "" ::= { traps 17 } connectMonitorAlarm NOTIFICATION-TYPE OBJECTS { connectMonitor } STATUS current DESCRIPTION "" ::= { traps 18 } connectMonitorNorm NOTIFICATION-TYPE OBJECTS { connectMonitor } STATUS current DESCRIPTION "" ::= { traps 19 } batteryConnectAlarm NOTIFICATION-TYPE OBJECTS { batCap } STATUS current DESCRIPTION "" ::= { traps 20 } batteryConnectNorm NOTIFICATION-TYPE OBJECTS { batCap } STATUS current DESCRIPTION "" ::= { traps 21 } batteryTemperatureLowNorm NOTIFICATION-TYPE OBJECTS { intTemp } STATUS current DESCRIPTION "" ::= { traps 22 } batteryTemperatureLowAlarm NOTIFICATION-TYPE OBJECTS { intTemp } STATUS current DESCRIPTION "" ::= { traps 23 } END