@@ -27,7 +27,7 @@ typedef enum {
|
|
|
ups_info, // 9 I\r
|
|
|
ups_rating_info, // 10 F\r
|
|
|
ups_remain_time_reg, // 11 Q2\r
|
|
|
- ups_general_status_req, // 12 QGS\r
|
|
|
+ ups_general_status_req, // 12 QGS\r [General status]
|
|
|
ups_akb_info, // 13 QBV\r
|
|
|
ups_model_req, // 14 QMD\r
|
|
|
ups_version_req, // 15 QVFW\r
|
|
@@ -38,7 +38,7 @@ typedef enum {
|
|
|
ups_passw_req, // 20 M\r
|
|
|
ups_buzzer_cntrl, // 21 PDA\r
|
|
|
ups_mode_req, // 22 QMOD\r
|
|
|
- ups_remote_turn_on, // 23 SON\r
|
|
|
+ ups_remote_turn_on, // 23 SON\r [Remote turn on UPS]
|
|
|
ups_warning_status, // 24 QWS\r
|
|
|
ups_bypass_volt_range, // 25 QBYV\r
|
|
|
ups_bypass_hvolt_264_set, // 26 PHV264\r
|
|
@@ -46,10 +46,85 @@ typedef enum {
|
|
|
ups_cmd_enable_flag_l, // 28 PEL\r
|
|
|
ups_kstar_status, // 29 BT\r
|
|
|
ups_temperature, // 30 QTPR\r
|
|
|
- ups_fault_status, // 31 QFS
|
|
|
- ups_remote_turn_off, // 32 SOFF
|
|
|
+ ups_fault_status, // 31 QFS [Fault status inquiry]
|
|
|
+ ups_remote_turn_off, // 32 SOFF [Remote turn off UPS]
|
|
|
|
|
|
MegaTec_cmd_max
|
|
|
|
|
|
} cmdMegaTecEnums_t;
|
|
|
-```
|
|
|
+```
|
|
|
+
|
|
|
+~={yellow}Сброс ошибки 13. Лог ручного сброса.=~
|
|
|
+[2025-03-24 11:26:07] Send: QGS
|
|
|
+[2025-03-24 11:26:07] [453ms] Return: (000.0 00.0 185.2 50.0 001.0 013 357.0 344.4 036.5 ---.- 069.1 101000000001
|
|
|
+[2025-03-24 11:26:11] Send: QGS
|
|
|
+[2025-03-24 11:26:12] [438ms] Return: (000.0 00.0 184.6 50.0 000.9 030 352.8 340.8 036.5 ---.- 069.2 101000000001
|
|
|
+[2025-03-24 11:26:16] Send: QGS
|
|
|
+[2025-03-24 11:26:16] [438ms] Return: (000.0 00.0 126.9 50.0 001.0 011 358.5 338.3 036.7 ---.- 069.2 101000000001
|
|
|
+[2025-03-24 11:26:20] Send: QGS
|
|
|
+[2025-03-24 11:26:21] [437ms] Return: (000.0 00.0 100.5 50.0 001.0 010 354.9 327.3 036.8 ---.- 069.2 101000000001
|
|
|
+[2025-03-24 11:26:25] Send: QGS
|
|
|
+[2025-03-24 11:26:25] [579ms] Return: (000.0 00.0 000.0 00.0 000.0 000 344.6 313.0 037.3 ---.- 069.3 101001000001
|
|
|
+[2025-03-24 11:26:59] Send: QFS
|
|
|
+[2025-03-24 11:27:00] [406ms] Return: (13 001.4 00.0 080.0 50.0 004 000.5 360.6 327.8 036.9 069.3 10100100
|
|
|
+[2025-03-24 11:33:29] Send: QGS
|
|
|
+[2025-03-24 11:33:30] [421ms] Return: (000.0 00.0 000.0 00.0 000.0 000 027.1 023.2 037.6 ---.- 053.0 101001000001
|
|
|
+[2025-03-24 11:33:30] The number of successful return: 65; Number of times to send commands: 65; Success rate: 100%
|
|
|
+[2025-03-24 11:33:38] Send: SOFF
|
|
|
+[2025-03-24 11:33:38] [187ms] Return: (ACK
|
|
|
+[2025-03-24 11:33:43] Send: SON
|
|
|
+[2025-03-24 11:33:43] [156ms] Return: (ACK
|
|
|
+[2025-03-24 11:33:49] Send: QGS
|
|
|
+[2025-03-24 11:33:50] [437ms] Return: (000.0 00.0 219.6 50.0 000.3 008 356.0 353.9 036.5 ---.- 052.1 101000000001
|
|
|
+[2025-03-24 11:33:57] Send: QGS
|
|
|
+[2025-03-24 11:33:57] [437ms] Return: (000.0 00.0 219.8 50.0 000.3 008 355.9 353.7 036.4 ---.- 051.8 101000000001
|
|
|
+
|
|
|
+~={yellow}Анализ пакета QGS=~
|
|
|
+
|
|
|
+000.0 00.0 185.2 50.0 001.0 013 357.0 344.4 0.365 ---.-- 069.1 101000000001
|
|
|
+000.0 - input voltage
|
|
|
+00.0 - input frequency
|
|
|
+185.2 - output voltage
|
|
|
+50.0 - output voltage
|
|
|
+001.0 - output current
|
|
|
+013 - positive BUS voltage
|
|
|
+357.0 - negative BUS voltage
|
|
|
+344.4 - P battery voltage
|
|
|
+0.365 - N battery voltage
|
|
|
+---.-- - Max temperature of the detecting pointers
|
|
|
+101000000001 - UPS status (b9 b8 b 7 b6 b5 b4 b3 b2 b1 b0 a0 a1)
|
|
|
+b9, b8 (00 - standby, 01 - line-interactive, 10 - on-line)
|
|
|
+b7 - utility fail
|
|
|
+b6 - battery low
|
|
|
+b5 - bypass/boost active
|
|
|
+b4 - UPS failed
|
|
|
+b3 - EPO
|
|
|
+b2 - test in progress
|
|
|
+b1 - shutdown active
|
|
|
+b0 - bat silence
|
|
|
+a0 - bat test FAIL
|
|
|
+a1 - bat test OK
|
|
|
+
|
|
|
+~={yellow}Анализ пакета QFS=~
|
|
|
+
|
|
|
+13 001.4 00.0 080.0 50.0 004 000.5 360.6 327.8 036.9 069.3 10100100
|
|
|
+
|
|
|
+13 - bus fault (inverter volt low)
|
|
|
+001.4 - I/P voltage is 208.3
|
|
|
+00.0 - I/P frequency
|
|
|
+080.0 - O/P voltage
|
|
|
+50.0 - O/P frequency
|
|
|
+004 - Load
|
|
|
+000.5 - O/P current
|
|
|
+360.6 - positive bus voltage
|
|
|
+327.8 - negative bus voltage
|
|
|
+036.9 - battery voltage
|
|
|
+069.3 - temperature
|
|
|
+b7 - DCTODC on
|
|
|
+b6 - PFC
|
|
|
+b5 - 1: inverter on
|
|
|
+b4 - reserved
|
|
|
+b3 - 1:input relay on
|
|
|
+b2 - 1:O/P relay on
|
|
|
+b1 - reserved always 0
|
|
|
+b0 - reserved always 0
|